NOTE: The storage of Petroleum Spirits and Mixtures is controlled by licence and the type of store provided for any material is subject to the consent and approval of the relevant Licensing Authority.
Where a chemical storage building is to be used as a high security store and the materials to be stored are non-toxic you may, subject perhaps to the recommendations of your Insurance Company, specify whichever type of store you feel would best suit your purpose.
Roof Construction
- Pre-cast Concrete - generally for external storage of petroleum spirits and mixtures and internal storage of H.F.L.
-
Fibre Cement - generally for external storage of H.F.L., L.P.G. and other substances.
CODE:
A - 2 hour fire resistance insulated
pre-cast concrete
B - 1 hour fire resistance insulated
pre-cast concrete.
C - ½ hour fire resistance pre-cast
concrete.
D - Non-combustible fibre cement sheets
to B.S.690
Wall Construction
A choice of three wall specifications is available to satisfy the period of fire resistance required, depending on the type of material stored, the location of the store and other factors.
CODE:
1 - 2 hour fire resistance insulated double pre-cast concrete .
2 - 1 hour fire resistance double pre-cast concrete.
3 - ½ hour fire resistance single pre-cast concrete.
Vents
The walls are provided with 230mm x 230mm cast-in galvanised vents to provide permanent ventilation at high and low level. Copper wire gauze flame arrestors fitted to the internal wall vents can be provided as an optional extra.
Fire Test Results
Tested in accordance with BS476 (Part 8)
a) Yarsley Testing Laboratories Ashtead Test No. C. 64240/1 Date: August 1977
b) Fire Research Station Boreham Wood Test No. FROSI NO.4513 Date: November 1967
Roof Construction
Span: 2.400m
Height: 2.000m
Lengths: from 1.200m to 7.200m in 600mm increments. Multiple length units are available with partition walls.
Particular requirements for the storage of Liquefied Petroleum Gases (LGP)
Having regard to the advice give in the 'Code of Practice for the keeping of Liquefied Petroleum Gas in cylinders and similar containers' published by the Health and Safety Executive, we supply chemical storage buildings for L.P.G. storage with the following modifications to the standard specification.
WALLS:
The H.S.E. Code of Practice recommends that walls of a purpose-built LPG store have a standard fire resistance of not less than 120 minutes.
DOORS:
Standard timber 1 hour fire resisting doors (single or double) over a 150mm high standard cill. Single doors have a clear opening size of 0.784m wide x 1.725m high (0.9m x 2.0m overall the frame) with Double doors 1.384m wide x 1.725m high (1.5m x 2.0m overall the frame).
VENTILATION:
The standard cast in vents are replaced by concrete louvres at both high and low level with a permanently ventilated area amounting to 2½% of the combined area of the walls and roof. Standard Specification includes one of the following:
Outward opening door, gloss painted red.
CODE: W - Timber, double, 1 hour fire resisting
Z - Timber, single, 1 hour fire resisting
150mm high liquid retention cill beneath door.
Warning sign.
CODE: 50 - PETROLEUM SPIRIT, HIGHLY FLAMMABLE, NO SMOKING OR NAKED LIGHTS
51 - PETROLEUM MIXTURE, HIGHLY FLAMMABLE, NO SMOKING OR NAKED LIGHTS
52 - HIGHLY FLAMMABLE, NO SMOKING OR NAKED LIGHTS
53 - L.P.G. HIGHLY FLAMMABLE
55 - NO SMOKING OR NAKED LIGHTS
56 - ACID
58 - AUTHORISED PERSONS ONLY Clause 2:1:4(b) of the H.S.E. Code recommends that a further total area of not less than 7½% of the combined total area of the walls and roof should be of light construction to allow for explosion relief. This requirement is met by roofing with fibre cement sheeting.
It should be recognised that every storage condition for LPG must be considered on its merits and that special circumstances, may necessitate variations from the general requirements of the Code of Practice, but for most situations the following recommended specifications will apply:
Corrugated fibre cement roof - Type 'D'
- 2 Hour fire resistance insulated pre-cast concrete double wall - Type '1'
- 1 hour fire resisting timber door - Type 'Z' (single), or type 'W' (double)
- Warning sign - Type '53'
|